MonitorFlow

How to monitor switches, printers, UPSs and other network devices

Watch what cannot run the agent: ping, TCP and UDP ports, and SNMP v2c or v3 for interfaces, traffic, UPS battery, temperatures and printer supplies, checked from a relay of the site or the central server.

Not everything can run the MonitorFlow agent. A switch, a router, a printer, a UPS or a NAS is still worth watching, and so is an address seen from somewhere else: a branch office that loses its link looks fine from inside and dead from the central server. MonitorFlow checks these over the network, from the relay of their site or from the central server, and alerts like for any server.

Why it matters

A switch port that goes down takes the servers behind it offline; a UPS that runs on battery gives you minutes, not hours; a printer out of toner stops an office. None of them sends an email on its own.

What MonitorFlow checks

Check What it measures Alert by default
Ping Whether the address answers, the round trip and the packet loss over a few pings Critical after 2 minutes without an answer, a warning above 20% loss for 5 minutes
TCP port Whether a port accepts connections Critical when it closes
UDP port A DNS or NTP server answering; for other ports, that the device does not refuse the packet Critical when it stops answering
SNMP Uptime, interfaces up or down, traffic in and out, errors and discards; processor, memory and storage; UPS battery, runtime and whether it is on battery; temperatures; printer supplies Depends on the kind of device, below

A UDP port that is not DNS or NTP has no answer to expect: MonitorFlow says it is up as long as the device does not refuse it. A port that stays silent and one blocked by a firewall look the same.

Add a device

  1. Open Fleet and click "Add a device".
  2. Give it a Name and its Address (an IP address or a DNS name).
  3. Checked from: the relay of its site is chosen when there is one. Choose the central server to see the device from outside.
  4. Keep "Ping it every minute…" ticked for a ping with its alerts.
  5. For SNMP, tick "Watch it over SNMP", enter the community (SNMP v2c) or the user, authentication and privacy passwords (SNMP v3, SHA and AES), then click "Detect": MonitorFlow asks the device what it answers and picks its Kind of device.
  6. Click "Add the device".

The device gets its own page, with its checks, their values and their alerts, and it can be silenced or put on a dashboard like a server. It is never shown as offline or waiting for an agent: its checks say what is wrong.

What each kind of device gets

Kind Checks Alerts
Switch SNMP, interfaces, temperatures No SNMP answer; a link above 90% for 10 minutes; more than one error a second; above 70 °C, critical above 80 °C
Router, Firewall SNMP, interfaces, processor and memory, temperatures The same, and the processor above 90%
NAS SNMP, interfaces, processor, memory and storage, temperatures Storage above 85%, critical above 95%
UPS SNMP, UPS battery Critical on battery, battery low, under 10 minutes of runtime
Printer SNMP, printer supplies A supply under 10%, critical under 2%
Generic SNMP, interfaces No SNMP answer; a link above 90%

An interface that is down raises nothing by default, since a switch's unused ports are down. To be told when one port goes down, add an alert on that interface from the device's page.

Change the credentials

On the device's page, open Details: the SNMP line says the version, the user and the port, never a password. "Change…" replaces them; a password left empty keeps the stored one.

When the alert fires

  • No SNMP answer: check the community or the v3 passwords, and that the device allows SNMP from the relay or the central server.
  • Ping fails from the relay but not from the central server (or the other way): the problem is on the network between them, not on the device.
  • On battery: the UPS lost mains power. Its runtime left says how long you have.

Your own servers' traffic

Servers with the agent measure the traffic, errors and drops of their own network interfaces too, with nothing to add: their Sensors tab has a row per interface.

This guide comes from the MonitorFlow repository. Suggest a change